Final | 5/24/2019 | 5/24/2019 | 5/24/2019 | A | PASS |
James Ady
|
|
|
Key should be under a block Phone #: ###-#### Inspection requested via web by Neal Rumsey Corrections made final ok
|
Final | 5/22/2019 | 5/23/2019 | 5/23/2019 | A | FAIL |
James Ady
|
|
|
front door should be open, or there is a key under a block in the entery Phone #: ###-#### Inspection requested via web by Neal Rumsey 210.52B1 Kitchen counter shall be served by 2 20A circuits. 406.9A Outdoor receps shall be type WR(Recp by a/c same recep is also dead.)
|
Rough-In Permanent Service | 11/8/2018 | 11/9/2018 | 11/9/2018 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Corrections fixed Rough-in ok to cover p/s o/h n ok
|
Rough-In Permanent Service | 11/6/2018 | 11/7/2018 | 11/7/2018 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey 225.32 Disc. means shall be nearest point of entry. Coductors shall comply with 230.6. 250.32. buildings supplied by branch shall have grounding electrode.
|
Issue PAID IN FULL permit | | | 11/6/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/6/2018 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|