Permit NumberELE18-04301
StatusFinaled
Name GLENN ELECTRIC
Site Address 2418 S TRAPPER PL
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: ROUGH & PERM SERVICE
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/26/20192/27/20192/27/2019APASS
DetailsJames Ady
code 4224 any ? call mike Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
Rough-In Permanent Service12/3/201812/3/201812/3/2018APASS
DetailsJames Ady
SPECS FOR HOOD VENT WILL BE ON SITE FOR REFERENCE Phone #: ###-#### Inspection requested via web by Bob Glenn Remote blower cable is a listed assembly and installed as per manufacturer instructions. Corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service11/28/201811/29/201811/29/2018PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Bob Glenn
110.3- All electrical equipment shall be listed for installation. Flexible cord for remote hood motor in 2nd floor attic does not have identification. Open conductors in attic to plug connection in attic. Shall be secured and supported. If listed shall be protected from damage where ran thru bored holes that do not maintain 1 1/4" from framing surface.
314.25- Recessed can in master bath over tub junction box cover shall be completely installed flush with box to totally cover box opening.
334 12 NM cable shall not be installed where subject to physical damage. Under stair installed where drywall will hit when it is installed.
Issue PAID IN FULL permit  11/7/2018 DONE
Payment received via Govolutions
Application received  11/7/2018 DONE
This permit was created on the web by Bob Glenn