Final | 11/28/2018 | 11/29/2018 | 11/29/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Stephen Morley..ok to final
|
Permanent Service | 11/22/2018 | 11/26/2018 | 11/26/2018 | P | PASS |
Tom Saunders
|
|
|
Idaho power is scheduled for the morning and we will call as soon as we are done. Phone #: ###-#### Inspection requested via web by Stephen Morley.... future pipe will remain empty grounding up dated...junction box used as feed thru for refeeding existing panel
p/s u/g reconnect ok
|
Conference | 11/20/2018 | 11/21/2018 | 11/20/2018 | A | PASS |
Tom Saunders
|
|
|
Shoot, I just missed the 11:30 deadline. Is there any way an inspector could come today? Inspection requested via web by Stephen Morley... discussed requirements for new meter base grounding needs updated 2 ground rods 6ft apart with #6 wire , expansion joint, intersystem bond bridge, and strapping pamphlet given...homeowner knowledgeable
|
Conference | 11/13/2018 | 11/15/2018 | 11/14/2018 | P | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### >> Inspection requested via web by Stephen Morley Inspection cancelled from web by: Stephen Morley
|
Issue PAID IN FULL permit | | | 11/13/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/13/2018 | | DONE |
|
|
|
This permit was created on the web by Stephen Morley
|