Final | 8/28/2019 | 8/29/2019 | 8/29/2019 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Correction complete, Final ok
|
Final | 8/23/2019 | 8/26/2019 | 8/26/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 356.30(1)- LFNC when installed in lengths greater than 6' shall have supports not to exceed 3' in length. AC 440.6- Overcurrent protection for AC unit shall not exceed value on name plate. 25 amp max 30 amp installed.
|
Rough-In Permanent Service | 5/24/2019 | 5/24/2019 | 5/24/2019 | P | PASS |
Rock A. Hudson
|
|
|
Tom Phone #: ###-#### Underground to service not connected to service. Garage rough in ok cover p/s u/g n ok
|
Electrical Rough-In | 12/1/2018 | 12/3/2018 | 12/3/2018 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI House only ok to cover
|
Issue PAID IN FULL permit | | | 12/1/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/1/2018 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|