Final | 12/11/2018 | 12/12/2018 | 12/12/2018 | A | PASS |
Tom Saunders
|
|
|
key box by front door code 3390 Phone #: ###-#### Inspection requested via web by Darryn Coburn...corrections made...ok to final
|
Telephone call | | | 12/11/2018 | | DONE |
|
|
|
Left voicemail asking for Darryn to call back to talk of work being done. Chose perm service but scope of work states remodel. Need to knokw if it is just a service change or if re wiring was done as well.
|
Final | 12/7/2018 | 12/10/2018 | 12/10/2018 | A | FAIL |
Tom Saunders
|
|
|
AC unit needs inspected. Key box by front door code 3390 Phone #: ###-#### Inspection requested via web by Darryn Coburn... 1..NM cable not approved to be used in wet or damp locations-334.12(B) A/C and service outlet 2..water heater shall have disconnect or breaker lock out installed 3..all outlets serving kitchen counter tops shall be/have GFCI protection-210.8 4..all garage outlets shall be/have GFCI protection-210.8 5..panel shall be legibally and completely labelled as to its clear, evident, and specific purpose or use-408.4
|
Issue PAID IN FULL permit | | | 12/7/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/7/2018 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|