Final | 5/29/2019 | 5/30/2019 | 5/30/2019 | A | PASS |
James Ady
|
|
|
House is unoccupied, lockbox on front door, coed is 470916 Phone #: ###-#### Inspection requested via web by Troy Cobb Corrections made final ok
|
Final | 5/29/2019 | 5/30/2019 | 5/29/2019 | A | CANC |
Rock A. Hudson
|
|
|
Front door should be unlocked, and house is unoccupied Phone #: ###-#### >> Inspection requested via web by Troy Cobb Inspection cancelled from web by: Troy Cobb
|
Final | 4/23/2019 | 4/24/2019 | 4/24/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Lockbox code is 470916 Phone #: ###-#### Inspection requested via web by Troy Cobb BCC 4-05-32- Code violations not to be retained. Remove exposed wire tapped off upstairs and luminaire on south east corner. 110.3- Receptacle outlet not working down wall from kitchen counter. 314.21- repair drywall so that gap around boxes does not exceed 1/8"
|
Electrical Rough-In | 1/18/2019 | 1/18/2019 | 1/18/2019 | P | PASS |
James Ady
|
|
|
Lockbox code is 470916 Phone #: ###-#### Inspection requested via web by Troy Cobb Whole house rewire. Not all walls opened up.Up S. Bed untouched. Basement is all storage and unfinished. Will add smokes where accessable. Rough in ok
|
Permanent Service | 12/13/2018 | 12/14/2018 | 12/14/2018 | A | PASS |
Rock A. Hudson
|
|
|
In case you need to get inside the access code is 470916 Phone #: ###-#### Inspection requested via web by Troy Cobb p/s o/h rec ok
|
Issue PAID IN FULL permit | | | 12/10/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/10/2018 | | DONE |
|
|
|
This permit was created on the web by Troy Cobb
|