Final | 7/11/2019 | 7/11/2019 | 7/11/2019 | P | PASS |
Tom Saunders
|
|
|
Code 8671 Phone #: ###-#### Inspection requested via web by Kotton Corder...corrections made...ok to final
|
Final | 7/10/2019 | 7/10/2019 | 7/10/2019 | P | FAIL |
Tom Saunders
|
|
|
Garage code 8671 Phone #: ###-#### Inspection requested via web by Kotton Corder... 1) all walls 2ft or larger shall have an outlet 2) all romex under 8ft ran horizontally shall be protected from physical damage 3) outlet shall be installed within 3ft of bath sink 4) a seperate circuit needs ran to ea disposal.. no load shall not exceed 80 percent of circuit
|
Rough-In Permanent Service | 12/19/2018 | 12/19/2018 | 12/19/2018 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kotton Corder.... rough ok to cover verify THHN ran to A/C units at final p/s u/g new ok
|
Issue PAID IN FULL permit | | | 12/19/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/19/2018 | | DONE |
|
|
|
This permit was created on the web by Kotton Corder
|