Final | 4/3/2019 | 4/4/2019 | 4/4/2019 | A | PASS |
Mark Moncarr
|
|
|
call for entry Phone #: ###-#### Inspection requested via web by Chris Berthelot Ok final. Looked at on 4/3/19
|
Rough-In Permanent Service | 12/22/2018 | 12/24/2018 | 12/24/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Chris Berthelot corrections made rough in ok
|
Rough-In Permanent Service | 12/21/2018 | 12/21/2018 | 12/21/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Chris Berthelot 210.70(A)(3)- Storage space under stairs shall ahve a lighting outlet installed controlled by a wall switch. 300.15- All NM cables shall terminate in a box or enclosure. Powder bath off entry not made up and up vacuum outlet. 334.12- NM calbe shall not be installed where subject to damage. 14-2 resting on fireplace. Provide clearance.
|
Issue PAID IN FULL permit | | | 12/21/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/21/2018 | | DONE |
|
|
|
This permit was created on the web by Chris Berthelot
|