Final | 5/7/2019 | 5/8/2019 | 5/8/2019 | A | PASS |
Mark Moncarr
|
|
|
property will be open, thank you Phone #: ###-#### Inspection requested via web by Darryn Coburn Ok final. Floor recept added top of stairs, GFI replaced in mstr bed for outside recepts.
|
Electrical Rough-In | 1/29/2019 | 1/29/2019 | 1/29/2019 | P | PASS |
James Ady
|
|
|
This request is for underground conduit and wiring. Phone #: ###-#### Inspection requested via web by Darryn Coburn underground from Garage to house ok to cover
|
Electrical Rough-In | 1/7/2019 | 1/8/2019 | 1/8/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ESC complaint from neighbor to east about no contact information posted on job site, trash and minimal property damage. Informed neighbor to document all damage alledged and damage is a civil matter. Called Andy Long about issue and he will come by on complaint inspection.
Dryer receptacle removed. Rough in ok cover
|
Permanent Service | 1/8/2019 | 1/8/2019 | 1/8/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Underground to service not in at time of inspection. p/s u/g n ok
|
Rough-In Permanent Service | 1/4/2019 | 1/7/2019 | 1/7/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Ronge receptacle will not be usable due to gas line installed in front of box. 300.15- 14-2 hanging in pantry shall terminate in a box. 590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protecton. All can locations to be a cut in LED recessed luminaire. Called contact, no answer, left message.
|
Issue PAID IN FULL permit | | | 12/26/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/26/2018 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|