First Notice | 3/13/2019 | 3/13/2019 | 4/23/2019 | | DONE |
Rock A. Hudson
|
|
|
|
Final | 3/13/2019 | 3/13/2019 | 3/13/2019 | P | PASS |
Rock A. Hudson
|
|
|
CONTACT: MIKE ENNIS Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok
|
Final | 3/12/2019 | 3/13/2019 | 3/13/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Contact: Mike Ennis Phone #: ###-#### Inspection requested via web by Deb Gooden 210.8(B)- 2 Circuits located in kitchen area on south end of bar shall have GFCI protection for personel.
|
Electrical Rough-In | 2/7/2019 | 2/8/2019 | 2/8/2019 | P | PASS |
Rock A. Hudson
|
|
|
Contact: Mike Ennis. PM ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Discussed requirement for show window receptacles and circuits. 2 windows with show receptacles noted on print, 2 window not shown on print. All window sections required to have show window receptacles and are wide enough to need dedicated circuits for each receptacle as per 210.62 and 220.14(G). Hardlid rough in ok cover
|
Electrical Rough-In | 1/15/2019 | 1/15/2019 | 1/15/2019 | P | PASS |
Rock A. Hudson
|
|
|
CONTACT: MIKE ENNIS Phone #: ###-#### Inspection requested via web by Deb Gooden 1 north and east windows will be roll up so no show window receptacles required. Wall rough in ok cover
|
Issue PAID IN FULL permit | | | 1/2/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/2/2019 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|