Final | 5/31/2019 | 6/3/2019 | 6/3/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Don Conley final ok
|
Final | 5/31/2019 | 5/31/2019 | 5/31/2019 | P | CANC |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Don Conley
|
Conference | 5/9/2019 | 5/9/2019 | 5/9/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Don Conley Talked about recep location over kitchen countertop to the left of cook top. Will put in plug mold on underside of cabinet.
|
Electrical Rough-In | 1/7/2019 | 1/7/2019 | 1/7/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Don Conley.... corrections made...rough ok to cover
|
Permanent Service | 1/7/2019 | 1/7/2019 | 1/7/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Don Conley....inspection done 1/4/19 by James Ady p/s u/g new ok
|
Electrical Rough-In | 1/3/2019 | 1/4/2019 | 1/4/2019 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Don Conley 210.52. Recep needed to rt of master bath pocket door and rt of living room slider. 300.4 Nail plates needed inkitchen rt of fridge and right of dining slider. 110.14. Grounding conductors needed tied through in smokes.
|
Issue PAID IN FULL permit | | | 1/3/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/3/2019 | | DONE |
|
|
|
This permit was created on the web by Don Conley
|