Final | 1/15/2019 | 1/15/2019 | 1/15/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan final ok
|
Permanent Service | 1/14/2019 | 1/15/2019 | 1/14/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan p/s u/g rec ok
|
Final | 1/9/2019 | 1/9/2019 | 1/9/2019 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan...
1...riser shall be strapped within 3ft of meter 2..expansion joint shall be added to riser 3..service grounding shall be brought up to code 2 groundrods 8ft apart
4.. bonding to gas pipe shall be removed
5.. a intersystem bond bridge shall be added to grounding system
5..permit fee shall be paid to full amount required for work being done 100A branch circuit was added to detach shop and not referenced in permit fee or explanation of scope of work
|
Issue PAID IN FULL permit | | | 1/7/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/7/2019 | | DONE |
|
|
|
This permit was created on the web by steve ragan
|