Permit Information
Permit NumberELE19-00090
StatusFinaled
Name NEW LEAF ELECTRIC
Site Address 700 S LATAH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Replacing the circuit wiring where they are still ungrounded, and replacing switches, receptacles and fixtures throughout the house.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/5/20193/5/20193/5/2019APASS
DetailsRock A. Hudson
Smoke detectors are now AFCI protected. Phone #: ###-#### Inspection requested via web by Dan Hilke Final ok
Final3/2/20193/4/20193/4/2019AFAIL
DetailsRock A. Hudson
Final was completed, but the permit was reopened so we could add a circuit for smoke detectors.
If there is no one at the house, you can call myself or Jim Thorpe (###-####) for access to get in. Phone #: ###-#### Inspection requested via web by Dan Hilke
210.12- A ll outlets located in bedroom areas shall have AFCI protection. Smoke detectors.
Final2/26/20192/27/20192/27/2019APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Dan Hilke
Final ok
Change Status to I  2/27/2019 DONE
change to ISS per Inspector-Eric
Final2/25/20192/26/20192/26/2019AFAIL
DetailsRock A. Hudson
Please give me 30 minutes notice to get there and open up the house. Phone #: ###-#### Inspection requested via web by Dan Hilke
210.12- All outlets located in bedroom areas shall have AFCI protection, device shall be located where circuit receives its source.
250.140- Range and dryer circuits shall be 4-wire. Frames of appliance shall have bond with seperate equipment grounds.
314.25- All boxes shall have covers. Receptacles, switches, lights hanging on wires.
406.12- All 120 volt 15 and 20 amp receptacles shall be tamper resistant type.
408.4- Circuit directory shall be complete.
422.31- Appliances shall have a disconnecting means. DW, WH. 110.25 lockouts acceptable. * Explained only licensed wireman employed by him are allowed to perform work.
* No smoke detectors installed.
* To remove receptacle from west soffit and cord that is attached that runs to back of garage.
Fees Due Hold1/26/2019 2/25/2019 DONE
Details
Telephone call  1/14/2019 DONE
Left voicemail for Dan to see what type of Misc. work is being donw. Scope of work shows it might be new branch circuits or branch circuit ext. ---update correct fixtures, inspection states they are doing all new wiring.
Electrical Rough-In1/7/20191/9/20191/9/2019PPASS
DetailsEric Story
This is the small house (rectory) in the back corner of the church parking lot. Phone #: ###-#### Inspection requested via web by Dan Hilke
Whole house re-wire ok
Only walls opened was kitchen and bases opened
Issue PAID IN FULL permit  1/7/2019 DONE
Payment received via Govolutions
Application received  1/7/2019 DONE
This permit was created on the web by Dan Hilke