Final | 4/2/2019 | 4/3/2019 | 4/3/2019 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Jose Guerrero Ok final.
|
Rough-In Permanent Service | 2/11/2019 | 2/11/2019 | 2/11/2019 | P | PASS |
Mark Moncarr
|
|
|
Contact contractor Jose Guerrero Phone #: ###-#### Inspection requested via web by Jose Guerrero Ok cover. Corrections made.
|
Rough-In Permanent Service | 2/10/2019 | 2/11/2019 | 2/11/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Contact contractor Jose Guerrero 2084075879 Phone #: ###-#### Inspection requested via web by Jose Guerrero 250.66- Grounding electrode conductor shall be sized to service entrance conductors. #4 minimum to underground water pipe. Shall connect where enters in basement and then bond cold and hot due to short pvc just inside house. 314.29- All boxes shall be accessible. Upstairs around back sliding glass door a junction is thrown up in soffit above slinding door and a jumper between out lights is run just under siding. Repair and recall.
|
Rough-In Permanent Service | 1/29/2019 | 1/29/2019 | 1/29/2019 | A | PASS |
Mark Moncarr
|
|
|
Please call to coordinate with contractor Jose Guerrero. Phone #: ###-#### Inspection requested via web by Jose Guerrero No RI inspeciton. p/s o/h n ok
|
Issue PAID IN FULL permit | | | 1/22/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/22/2019 | | DONE |
|
|
|
This permit was created on the web by Jose Guerrero
|