First Notice | 3/6/2019 | 3/6/2019 | 4/11/2019 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Scott Campbell
|
Final | 3/6/2019 | 3/6/2019 | 3/6/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Noll Final ok
|
Final | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | CANC |
Rock A. Hudson
|
|
|
can this please be the last inspection time for the day if possible. thanks Phone #: ###-#### Inspection requested via web by Jim Noll Jim Noll called and asked to cancel inspection and they would recall. Thanks for heads up.
|
Final | 3/5/2019 | 3/5/2019 | 3/5/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Noll Corrections not all complete. Open boxes up mech., open boxes above stage floor. (Trouble shooting)
|
Final | 3/4/2019 | 3/4/2019 | 3/4/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Noll 110.14- Unused openings shall be closed. KO seals electrical room, up stairs mezz, up near bar. 210.62- Show window receptacles required on all windows with 12 linear ft or major fraction there of. 3 entrance windows above doors. 300.15- All splices shall be contained in boxes. Dn hall to bathrooms, up near bar. 314.25- All boxes shall have covers, Entry desk, up mech. up near bar.
|
Final | 3/1/2019 | 3/1/2019 | 3/1/2019 | P | CANC |
Rock A. Hudson
|
|
|
please call when you have a time scheduled to come and inspect. thanks Phone #: ###-#### Inspection requested via web by Jim Noll Jim Noll called and asked to cancel and would reschedule when ready. Thank you for the heads up.
|
Conference | 2/28/2019 | 2/28/2019 | 2/28/2019 | P | PASS |
Rock A. Hudson
|
|
|
Discussed work clearance required for disconnecting means for upstairs mechenical equipment in small room. As per 110.26 minimum width and depth shall be present. As of now 24" width for 2 unfused disconnects.
|
Conference | 2/6/2019 | 2/6/2019 | 2/6/2019 | P | PASS |
Rock A. Hudson
|
|
|
Discusssed if conduit run from disconnect to transformer is required to stay out of work space associated with disconnecting means. As per 110.26- work space shall be clear from floor to 6 1/2' minimum height and minimum width and depth of space depending on voltage in front of disconnecting means.
|
Electrical Rough-In | 2/6/2019 | 2/6/2019 | 2/6/2019 | A | PASS |
Rock A. Hudson
|
|
|
The Knitting Factory wall inspection in concert area. Dimitri Gyteas on site contact. Phone #: ###-#### Inspection requested via web by Jim Noll North and south pathway lights and receptacles wall rough in ok cover
|
Issue PAID IN FULL permit | | | 1/28/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/28/2019 | | DONE |
|
|
|
This permit was created on the web by Scott Campbell
|