Temporary Service | 2/4/2019 | 2/5/2019 | 2/5/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Schaffer t/s u/g n ok
|
Temporary Service | 2/3/2019 | 2/4/2019 | 2/4/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Schaffer 230.62- Live parts shall be guarded from accidental contact. 3 out of 4 cover screws missing. 250.24- Grounded conductor shall be connected to a grounding electrode conductor. Unable to locate main bonding jumper.
|
Issue PAID IN FULL permit | | | 2/3/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/3/2019 | | DONE |
|
|
|
This permit was created on the web by Ryan Schaffer
|