Final | 3/6/2020 | 3/6/2020 | 3/6/2020 | P | PART |
Rock A. Hudson
|
|
|
Changing out the exits today. Please come as late as possible or call 1/2 prior to arrival. Danny is the contact. Thanks Phone #: ###-#### Inspection requested via web by Buster Bowen Card signed. TCO OK
|
Final | 3/5/2020 | 3/5/2020 | 3/5/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 110.3(B)- Exit lights shall have an operating temp for the environment for which it is installed. 0 degrees celcius to 50 degrees celcius, 32 degrees F to 104 degrees F installed. -40 degrees C to 50 degrees C on order. 110.26(D)- Illumination around electrical service and panel boards shall not be controlled by automatic means. Fire alarm circuit breaker is located in a hotel electrical room which is under construction, illumination required.
|
Conference | 2/24/2020 | 2/24/2020 | 2/24/2020 | P | PASS |
Rock A. Hudson
|
|
|
Pre TCO walk thru- - Fire pump replacement being installed due to manufacturing issues. - Must complete panel schedules. - Level 2 12"x12" junction has low volt cables not rated for other voltages present in box. - Elevator yet to complete and inspect. - Damp location rated receptacles and cover thru out parking garage. - Exposed wiring for signs shall be terminated in boxes with covers. - Commissioning report required for generator and lighting systems. - Label all disconnecting means as to each purpose. 2 located level 6 to 7 on stair tower. - Ticket stations not in as of 2/24/2020 4pm. - Stairways have not officially been inspected but appear to have all lighting complete.
|
Electrical Rough-In | 2/3/2020 | 2/5/2020 | 2/4/2020 | A | CANC |
Rock A. Hudson
|
|
|
Underground cover for 5th street side historic pole lights. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Duplicate request.
|
Electrical Rough-In | 2/4/2020 | 2/4/2020 | 2/4/2020 | P | PASS |
Rock A. Hudson
|
|
|
Underground cover 5th street side. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 2 east pole bases and underground for poles and extend to south rough in ok cover.
|
Electrical Rough-In | 2/3/2020 | 2/4/2020 | 2/3/2020 | A | CANC |
Rock A. Hudson
|
|
|
Underground cover. 5th street side for historic street lights. Phone #: ###-#### >> Inspection requested via web by Buster Bowen Inspection cancelled from web by: Buster Bowen
|
Electrical Rough-In | 1/27/2020 | 1/27/2020 | 1/27/2020 | P | PASS |
Rock A. Hudson
|
|
|
Garage Soffit cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Garage interior soffits rough in ok cover
|
Conference | 1/17/2020 | 1/17/2020 | 1/17/2020 | P | DONE |
Rock A. Hudson
|
|
|
Discussed the occupancy of parking garage in 30 days. General contractor will meet with city officials to determine a completion plan. BLD18-01831 states several subs will finish on hotel phase including electrical lighting and emergency lighting, generator back up, elevators, egress paths ect. Completion plan will determine what systems must be complete.
|
Permanent Service | 1/1/2020 | 1/2/2020 | 1/2/2020 | A | PASS |
Rock A. Hudson
|
|
|
Permanent service. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Main service and fire pump service ok p/s u/g n ok
|
Electrical Rough-In | 12/23/2019 | 12/23/2019 | 12/23/2019 | P | PASS |
Eric Story
|
|
|
Pole Base pour. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen 7th floor pole bases ok to cover
|
Electrical Rough-In | 12/13/2019 | 12/16/2019 | 12/16/2019 | P | PASS |
Rock A. Hudson
|
|
|
7th floor PT deck cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Last pour noted rough in ok cover
|
Electrical Rough-In | 12/11/2019 | 12/11/2019 | 12/11/2019 | P | PASS |
Eric Story
|
|
|
6th floor Stair Tower. After 2pm if possible. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 6th floor elevator shaft ok to cover
|
Electrical Rough-In | 12/5/2019 | 12/5/2019 | 12/5/2019 | P | PASS |
Rock A. Hudson
|
|
|
7th Floor NW stair tower. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Discussed running service entrance conductors assciated with fire pump on interior of building. Shall comply with 230.6. Level 7 area noted rough in ok cover
|
Electrical Rough-In | 11/22/2019 | 11/25/2019 | 11/25/2019 | P | PASS |
Rock A. Hudson
|
|
|
6th floor east PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Pour noted rough in ok cover
|
Electrical Rough-In | 11/20/2019 | 11/20/2019 | 11/20/2019 | P | PASS |
Rock A. Hudson
|
|
|
NW Stair Tower cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level 6 N.W. stair pour rough in ok cover
|
Electrical Rough-In | 11/14/2019 | 11/14/2019 | 11/14/2019 | P | PASS |
Rock A. Hudson
|
|
|
6th floor west PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level 5 to 6 north and west pour rough in ok cover
|
Electrical Rough-In | 11/11/2019 | 11/12/2019 | 11/12/2019 | A | PASS |
Rock A. Hudson
|
|
|
SE Stair tower in garage. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Stairway noted pour rough in ok cover
|
Electrical Rough-In | 11/1/2019 | 11/1/2019 | 11/1/2019 | P | PASS |
Rock A. Hudson
|
|
|
5th floor PT deck cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Level 5 south and east PT deck pour rough in ok cover.
|
Electrical Rough-In | 10/25/2019 | 10/25/2019 | 10/25/2019 | P | PASS |
Rock A. Hudson
|
|
|
Cover for 5th floor NW stair tower. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Area noted rough in ok cover
|
Electrical Rough-In | 10/21/2019 | 10/21/2019 | 10/21/2019 | P | PASS |
Rock A. Hudson
|
|
|
5th Floor PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level noted on north and west sides pour rough in ok cover.
|
Electrical Rough-In | 10/16/2019 | 10/16/2019 | 10/16/2019 | P | PASS |
Rock A. Hudson
|
|
|
Cover for SE stairwell in garage. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level 4 S.E. stairwell rough in ok cover
|
Electrical Rough-In | 10/3/2019 | 10/7/2019 | 10/7/2019 | P | PASS |
Rock A. Hudson
|
|
|
4th floor PT deck pour. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Level 4 ramp and around east side pour rough in ok cover
|
Electrical Rough-In | 10/1/2019 | 10/2/2019 | 10/2/2019 | A | PASS |
Rock A. Hudson
|
|
|
4th floor NW Stairwell cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level noted stair walls rough in ok cover
|
Electrical Rough-In | 9/25/2019 | 9/25/2019 | 9/25/2019 | P | PASS |
Rock A. Hudson
|
|
|
Shear wall cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Shear wall level 2 south east corner rough in ok cover
|
Electrical Rough-In | 9/23/2019 | 9/23/2019 | 9/23/2019 | P | PASS |
Rock A. Hudson
|
|
|
PT deck concrete pour. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen PT deck ramp from level 3 to 4 and around to south on west side pour rough in ok cover.
|
Electrical Rough-In | 9/16/2019 | 9/16/2019 | 9/16/2019 | P | PASS |
Rock A. Hudson
|
|
|
Garage stairwell. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Levels 3 to 4 South East stair wall rough in ok cover
|
Electrical Rough-In | 9/6/2019 | 9/9/2019 | 9/9/2019 | P | PASS |
Eric Story
|
|
|
Garage PT deck pour. Buster is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen 3rd floor PT deck ok to pour
|
Electrical Rough-In | 8/28/2019 | 8/28/2019 | 8/28/2019 | P | PASS |
James Ady
|
|
|
Cover for 3rd floor NW Stairwell. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Walls only area listed ok to cover
|
Electrical Rough-In | 8/23/2019 | 8/23/2019 | 8/23/2019 | P | PASS |
Rock A. Hudson
|
|
|
Deck pour cover. Tyson is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level 2 to 3 ramp and level 3 deck pour rough in ok cover.
|
Electrical Rough-In | 8/16/2019 | 8/16/2019 | 8/16/2019 | P | PASS |
Rock A. Hudson
|
|
|
Garage Stairwell cover. Tyson is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen S.E. stair well level 2 walls rough in ok cover
|
Electrical Rough-In | 8/7/2019 | 8/7/2019 | 8/7/2019 | P | PASS |
Rock A. Hudson
|
|
|
Wall cover for NW stairwell. Tyson is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Area noted rough in ok cover
|
Electrical Rough-In | 8/5/2019 | 8/5/2019 | 8/5/2019 | P | PASS |
Rock A. Hudson
|
|
|
PT deck pour from level 2 to 3 rough in ok cover
|
Electrical Rough-In | 8/2/2019 | 8/5/2019 | 8/5/2019 | P | NH |
Rock A. Hudson
|
|
|
Danny PT deck concrete pour at front street garage. Phone #: ###-#### Inspection requested via web by Sean DeLacy Contact provided is on bereavement leave due to the death of his daughter. Undable ot locate others on site. Provide correct contact number so I do ot have to bother this person again.
|
Electrical Rough-In | 7/15/2019 | 7/16/2019 | 7/16/2019 | P | PASS |
Rock A. Hudson
|
|
|
Garage concrete pour cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Report has been given of someone with general contractor removing electrical conduits with out informing electrical contractor. BCC 4-05-15 It shall be unlawful for any person to engage in electrical work without first having a electrical journeymans license and be employed by an electrical licenced and permitted electrical contractor. First and only warning, if any electrical wiring , conduit, or equipment is installed or removed without consulting electrical foreman of licensed and permitted electrical contractor a compliance inspector from the State of Idaho will be brought on site to discuss penalties and fines up to $1000 that may be assessed for each infraction. Level 2 west pour as noted on contractor print rough in ok cover
|
Electrical Rough-In | 6/18/2019 | 6/18/2019 | 6/18/2019 | P | PASS |
Rock A. Hudson
|
|
|
Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen EMT being used with taped up boxes and fittings as per instructions. Bottom of ramp pour rough in ok cover
|
Electrical Rough-In | 5/8/2019 | 5/8/2019 | 5/8/2019 | P | PASS |
Rock A. Hudson
|
|
|
UG inspection. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Garage underground complete, west of line 9 rough in ok cover
|
Electrical Rough-In | 5/6/2019 | 5/6/2019 | 5/6/2019 | P | PASS |
Daryl DeGrange
|
|
|
UG cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Rough-in ok cover between A-D 1 thur 9
|
Electrical Rough-In | 4/26/2019 | 4/26/2019 | 4/26/2019 | P | PASS |
Rock A. Hudson
|
|
|
UG inspection. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen East parking garage underground roug in ok cover.
|
Electrical Rough-In | 4/17/2019 | 4/18/2019 | 4/18/2019 | A | PASS |
Rock A. Hudson
|
|
|
NW Concrete Stairwell rough in. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Area noted pour rough in ok cover
|
Electrical Rough-In | 4/8/2019 | 4/9/2019 | 4/9/2019 | A | PASS |
Rock A. Hudson
|
|
|
Cover for NE concrete walls. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen N.E. corner wall pour rough in ok cover
|
Electrical Rough-In | 4/2/2019 | 4/2/2019 | 4/2/2019 | P | PASS |
Mark Moncarr
|
|
|
Wall rough. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Ok cover conduits SE hotel stairwell.
|
Electrical Rough-In | 4/1/2019 | 4/1/2019 | 4/1/2019 | P | PASS |
Rock A. Hudson
|
|
|
Wall rough for garage. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen South East stair wall pour rough in ok cover
|
Electrical Rough-In | 2/19/2019 | 2/19/2019 | 2/19/2019 | P | PASS |
Rock A. Hudson
|
|
|
Uffer inspection. Danny is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen Concrete encased electode rough in ok cover
|
Issue PAID IN FULL permit | | | 2/18/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/18/2019 | | DONE |
|
|
|
This permit was created on the web by Sean DeLacy
|