Print Statement | | | 1/29/2020 | | DONE |
|
|
|
|
Final | 8/28/2019 | 8/29/2019 | 8/29/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...ok to final...card signed
|
Permanent Service | 8/18/2019 | 8/19/2019 | 8/19/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 250.24(A)(1)- Concrete encased grounding electrode conductor to be relocated to same terminal or bus grounded conductor is terminated. 250.52(B)(3)- Underground metal gas piping shall not be used as a grounding electrode. 250.104(B)- Bonding of gas piping needed if likely to become energized. House panel ok p/s u/g n ok
|
Electrical Rough-In | 7/25/2019 | 7/25/2019 | 7/25/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...electrical and fire riser room walls only
|
Electrical Rough-In | 7/19/2019 | 7/22/2019 | 7/22/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton... exterior soffit cans..2 locations...ok to cover
|
Electrical Rough-In | 7/12/2019 | 7/15/2019 | 7/15/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...underground for pole lights front and back of building
|
Electrical Rough-In | 7/3/2019 | 7/3/2019 | 7/3/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...underground for parking lot lights and LV to building
|
Electrical Rough-In | 6/20/2019 | 6/21/2019 | 6/21/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton... underground feeds from ID power transformer ID Power true inspection...verified by Boise City inspector
|
Electrical Rough-In | 3/7/2019 | 3/8/2019 | 3/8/2019 | A | PASS |
Rock A. Hudson
|
|
|
Please call Bob at ###-#### first thing in the morning. Thanks Phone #: ###-#### Inspection requested via web by Kerri Hamilton North east corner under slab rough in ok cover
|
Electrical Rough-In | 3/1/2019 | 3/1/2019 | 3/1/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton... uffer ground ok
|
Electrical Rough-In | 2/20/2019 | 2/20/2019 | 2/20/2019 | A | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...Kerri called and requested be cancelled due to weather
|
Issue PAID IN FULL permit | | | 2/20/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/20/2019 | | DONE |
|
|
|
This permit was created on the web by Kerri Hamilton
|
First Notice | 8/29/2019 | 8/29/2019 | | | |
Tom Saunders
|
|
|
|