Final | 6/28/2019 | 7/1/2019 | 7/1/2019 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga Ok final. Corrections made. Outlet buried in dining, now installed.
|
Final | 6/3/2019 | 6/4/2019 | 6/4/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga 210.8- All 15 or 20 amp 120 volt receptacle outets installed with in 6' of a sink shall have GFCI protection. Washer. 210.52(A)- No point measured along floor line shall be more than 6' from a receptacle outlet. Dining area. 210.70- A luminaire shall be installed on the exterior of each doorway with exterior access. Garage mandoor. 410.16- Incandescent and LED luminaires shall not be installed with in 12" of storage shelf in a clothes closet. * Fee due- Fee charged was for service only, additional $80 due for dwelling totalling $135.
|
Rough-In Permanent Service | 2/27/2019 | 2/28/2019 | 2/28/2019 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga p/s u/g n ok
|
Issue PAID IN FULL permit | | | 2/21/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/21/2019 | | DONE |
|
|
|
This permit was created on the web by Greg Idsinga
|