Print Statement | | | 10/23/2019 | | DONE |
|
|
|
|
First Notice | 5/1/2019 | 5/1/2019 | 5/6/2019 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Lee VanSchoiack
|
Final | 4/30/2019 | 5/1/2019 | 5/1/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
|
Final | 4/30/2019 | 4/30/2019 | 4/30/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack 210.8- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Bar. 22/24 2 pole 20 for kitchen not tripping. 300.22- Cooler penatrations shall be sealed. 408.4- Circuit directory shall be complete.
|
Electrical Rough-In | 4/24/2019 | 4/24/2019 | 4/24/2019 | P | PASS |
Rock A. Hudson
|
|
|
Grid ceiling Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Bar grid rough in ok cover
|
Electrical Rough-In | 4/19/2019 | 4/19/2019 | 4/19/2019 | P | PART |
Rock A. Hudson
|
|
|
grid ceiling Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Kitchen and office grid only rough in ok cover
|
Electrical Rough-In | 3/11/2019 | 3/12/2019 | 3/12/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Hardlids, bar wall, columns rough in ok cover
|
Electrical Rough-In | 2/21/2019 | 2/22/2019 | 2/22/2019 | P | PASS |
Mark Moncarr
|
|
|
office, kitchen, bathroom walls Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Ok cover office, baths and kitch area.
|
Issue PAID IN FULL permit | | | 2/21/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/21/2019 | | DONE |
|
|
|
This permit was created on the web by Lee VanSchoiack
|