Print Statement | | | 9/25/2019 | | DONE |
|
|
|
|
First Notice | 7/22/2019 | 7/22/2019 | 7/22/2019 | | DONE |
James Ady
|
|
|
This permit finaled on the web by Debby Pierce
|
Final | 7/19/2019 | 7/22/2019 | 7/22/2019 | A | PASS |
James Ady
|
|
|
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Corrections made final ok
|
Final | 7/17/2019 | 7/18/2019 | 7/18/2019 | A | FAIL |
James Ady
|
|
|
Bill Peace is contact at ###-####, Temp Final?? Phone #: ###-#### Inspection requested via web by Debby Pierce 110.3B and 210.8. Rm 106A nurses Breakroom. Recep on wall Reverse polarity and no GFCI within 6ft of sink. Rm 130- Existing receps on back wall are dead. Kitchen- BBC Section 9-05-32. Violation not to be retained. 110.12A Unused openings shall be closed(Missing KO seal in heater J-Box) 210.8B2. Kitchen receps shall be GFCI protected.(Remove or protect existing receps in kitchen area)
|
Electrical Rough-In | 6/13/2019 | 6/14/2019 | 6/14/2019 | A | PASS |
James Ady
|
|
|
Ceiling Inspection, Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce rooms 130 and 102 Ceiling only ok to cover
|
Electrical Rough-In | 6/11/2019 | 6/12/2019 | 6/12/2019 | A | PASS |
James Ady
|
|
|
Bill Peace is contact at ###-####. Ceiling Inspection. Phone #: ###-#### Inspection requested via web by Debby Pierce Room 132 ceiling only ok to cover
|
Electrical Rough-In | 5/3/2019 | 5/6/2019 | 5/6/2019 | A | PASS |
James Ady
|
|
|
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce room 106A hard lid ok to cover
|
Electrical Rough-In | 5/2/2019 | 5/3/2019 | 5/3/2019 | A | PART |
James Ady
|
|
|
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce 3 Restrooms Ceiling only Ok to cover. 106A Nurses restroom not ready. Burried j box at ceiling.
|
Electrical Rough-In | 4/16/2019 | 4/17/2019 | 4/17/2019 | A | PASS |
James Ady
|
|
|
Andy Chambers is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Classroom devider wall and restroom ok to cover
|
Electrical Rough-In | 4/12/2019 | 4/12/2019 | 4/12/2019 | P | PASS |
James Ady
|
|
|
Andy Chambers is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Classroom and 2 restrooms, Hard lids only access panels framed ok to cover
|
Electrical Rough-In | 4/9/2019 | 4/10/2019 | 4/10/2019 | A | PASS |
James Ady
|
|
|
Andy Chambers is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Discussed GFCI requirments for kitchen. Half wall in Kitchen only ok to cover
|
Issue PAID IN FULL permit | | | 3/4/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 3/4/2019 | | |
|
|
|
|
Application received | | | 3/4/2019 | | DONE |
|
|
|
This permit was created on the web by Debby Pierce
|