Final | 5/7/2019 | 5/8/2019 | 5/8/2019 | A | PASS |
Eric Story
|
|
|
the breaker tie down is installed, it is a new style, its a black plastic piece top center of the panel over the main breaker, please call for any questions, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Corrections fixed final ok
|
Final | 5/1/2019 | 5/2/2019 | 5/2/2019 | A | FAIL |
Eric Story
|
|
|
Ant questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren 210.63 Air conditionning equipment shall have a receptacle located within 25' of equipment 408.36(d) Back fed devices shall be secured in place 250.94(a) Intersystem bond device required
|
Rough-In Permanent Service | 3/5/2019 | 3/6/2019 | 3/6/2019 | A | PASS |
Tom Saunders
|
|
|
Any questions plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren... rough in ok to cover p/s o/h new ok
|
Issue PAID IN FULL permit | | | 3/4/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/4/2019 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|