Final | 5/10/2019 | 5/10/2019 | 5/10/2019 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Sherry Allen Final ok, card signed
|
Permanent Service | 4/25/2019 | 4/26/2019 | 4/26/2019 | A | PASS |
Eric Story
|
|
|
This is for a service inspection on first hanger. A conduit and trench inspection also please. Phone #: ###-#### Inspection requested via web by Sherry Allen p/s u/g n ok Will clone a rough-in for conduit and ground rods
|
Electrical Rough-In | 4/26/2019 | 4/26/2019 | 4/26/2019 | P | PASS |
Eric Story
|
|
|
This is for a service inspection on first hanger. A conduit and trench inspection also please. Phone #: ###-#### Inspection requested via web by Sherry Allen U/G and buried ground rods ok to cover
|
Permanent Service | 4/23/2019 | 4/24/2019 | 4/24/2019 | A | FAIL |
Eric Story
|
|
|
inspection service/permanent on first hangar. separate job from temporary pole. Phone #: ###-#### Inspection requested via web by Sherry Allen Shall not use IDCO transformer as sole source of grounding electrode system 250-54 Shall have a supplementary electrode (rods) for grounding electrode system
|
Permanent Service | 4/22/2019 | 4/23/2019 | 4/23/2019 | A | CANC |
Eric Story
|
|
|
This is for a service inspection. Please call Bill @ ###-#### prior to arrival Phone #: ###-#### Inspection requested via web by Sherry Allen
|
Issue PAID IN FULL permit | | | 3/6/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/6/2019 | | DONE |
|
|
|
This permit was created on the web by Sherry Allen
|
First Notice | 5/10/2019 | 5/10/2019 | | | |
Eric Story
|
|
|
|