Final | 9/25/2019 | 9/26/2019 | 9/26/2019 | A | PASS |
Tom Saunders
|
|
|
corections made and house is ready for final code is 4646enter Phone #: ###-#### Inspection requested via web by ron spen cer... corrections made...ok to final
|
Final | 9/23/2019 | 9/24/2019 | 9/24/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer 200.6- White conductor used as other than grounded conductor shall be identified other than white in AC disconnect. 210.8(A)- Unable to located GFCI device for christmas receptacle in soffit, exception to outdoor receptacle fed off garage circuit is for readily accessible receptacles only. 210.52(A)- Area above cabinets at each side of fireplace is wall space and shall have a receptacle outlet located with in 6' of fire place. Receptacles located inside cabinets do not count. 210.52(C)- Counter top located in pantry shall have receptacles installed so that at no point measured along wall line is more than 24" from a receptacle outlet. 210.70- Required luminaire located at garage man door not working. 314.23(B)(1)- Island receptacle boxes shall not be secured by screws thru side of boxes. 334.30- NM cable shall be secured with in 12" of island receptacle box. 352.30- PVC service riser shall be secured with in 3' of meter base. strap in place but not secured. 406.6- Outdoor receptacle in use cover on east side of garage not completely secured. Missing screw. BCC 9-05-17- It shall be unlawful to block electrical inspectors access to electracal associated with dwelling. Move master bed dresser and bed a minimum of 3' from wall to provide access to receptacles.
|
Rough-In Permanent Service | 3/12/2019 | 3/12/2019 | 3/12/2019 | P | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer... corrections made rough ok to cover p/s u/g new ok
|
Rough-In Permanent Service | 3/11/2019 | 3/11/2019 | 3/11/2019 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer... 1..temp outlets installed with screws not approved for box...box shall be replaced..110.3 2..wire shall be free of pinch points and away from truss gang nailers...throughout house..110.12 3..NM cable shall be supported to code...334.30 every 4 1/2 ft. mst bedroom, entry, above panel 4..smoke detectors shall be made up-grounds connected
|
Issue PAID IN FULL permit | | | 3/11/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/11/2019 | | DONE |
|
|
|
This permit was created on the web by ron spen cer
|