Final | 8/29/2019 | 8/30/2019 | 8/30/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Daniel Dow Corrections made final ok
|
Final | 8/15/2019 | 8/16/2019 | 8/16/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Daniel Dow 210.8- All receptacles serving kitchen counter top areas shall have GFCI protection. Left of sink. 314.17- Where NM cable enters boxes sheathing shall enter box a minimum of 1/4". Island. Where NM cable enters a metal enclosure abrasion protection shall be provided. AC disconnect. 334.12- NM cable shall not be installed where subject to damage. Island, need conduit protection. 356.30- Non metallic flex shall be secured with in 12" of enclosure. AC whip. 406.5- Receptacles shall be secured to boxes. 1 rt of fireplace and basement family room. 406.9- Outdoor covers shall be extra duty rated. 408.4- Circuit directory shall be complete. 440.6- AC fuse shall not exceed value on name plate. 40 installed 35 max.
|
Electrical Rough-In | 3/22/2019 | 3/22/2019 | 3/22/2019 | P | PASS |
Rock A. Hudson
|
|
|
Daniel Phone #: ###-#### Master bed only new bedroom circuit. Smokes on master bedroom circuit. Rough in ok cover
|
Override - Parcel Holds | 3/22/2019 | 1/1/1900 | 3/22/2019 | | |
|
|
|
this is the electrical rough-in
|
Conference | 3/20/2019 | 3/20/2019 | 3/20/2019 | P | DONE |
James Ady
|
|
|
Daniel Phone #: ###-#### Covered a lot of topics. Owner has done Electrical work before. Covers needed on all atttic J boxes, receps needed on all patios, Smoke detectors need added.
|
Override - Parcel Holds | 3/20/2019 | 1/1/1900 | 3/20/2019 | | |
|
|
|
this is not the building permit, only wants conference for ele
|
Override - Parcel Holds | 3/19/2019 | 1/1/1900 | 3/19/2019 | | |
|
|
|
Electrical Inspection
|
Issue PAID IN FULL permit | | | 3/11/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/11/2019 | | DONE |
|
|
|
This permit was created on the web by Daniel Dow
|