Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-00894
StatusFinaled
Name B & B ELECTRIC
Site Address 617 S ASH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Service Change Overhead to underground
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/10/20195/10/20195/10/2019PPASS
DetailsRock A. Hudson
HAYMAN HOUSE, PLEASE CALL TO SET UP TIME TO GET IN. Phone #: ###-#### Inspection requested via web by mike brown
Areas of concern-
394.12- Existing knob and tube wiring has had insulation installed round conductors. Wiring method requires wiring to not be in contact with thermo-insulation to provent overheating.
406.4(D)- Grounding type receptacle outets installed on ungrounded branch circuits. Grounding type receptacles on ungrounded shall be GFCI protected or changed to 2 wire receptacles.
Final ok
Permanent Service4/16/20194/17/20194/17/2019PPASS
DetailsRock A. Hudson
IMPORTANT: CALL TOM BROWN (###-####) FOR ACCESS AND TIME Phone #: ###-#### Inspection requested via web by Bonnie Page
Note concerns of knob and tube in contact with insulation on final.
p/s u/g n ok
Issue PAID IN FULL permit  3/14/2019 DONE
Payment received via Govolutions
Application received  3/14/2019 DONE
This permit was created on the web by Bonnie Page