Permit Information
Permit NumberELE19-00895
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 2015 N CURTIS RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: NEW CAFETERIA
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Statement  1/9/2020 DONE
Final10/17/201910/18/201910/18/2019APASS
DetailsMark Moncarr
Brett is the contact. Phone #: ###-#### Inspection requested via web by Deb Ipsen Ok final. Fuses for roof top unit changed out, GFI protection provided at areas listed.
Final9/25/20199/26/20199/26/2019PPART
DetailsRock A. Hudson
Electrical final, Brett is the contact. Phone #: ###-#### Inspection requested via web by Deb Ipsen
210.8(B)- All 120 volt receptacles located in kitchen area shall have GFCI protection. Left of serving window and right of ovens on 1/2 wall.
440.6- Fuse for small roof top unit min fuse over 30 amp, 30 amp fuses installed in disconnect.
Contractor to correct by the time we do an AM fly by.
Ovens from existing kitchen to be brought over at future time. Will need to verify these connections.
TCO OK
Electrical Rough-In9/17/20199/19/20199/19/2019APASS
DetailsTom Saunders
Ceiling rough in... Shannon is the contact Phone #: ###-#### Inspection requested via web by Deb Ipsen...ok to cover
Electrical Rough-In9/17/20199/18/20199/17/2019ACANC
DetailsTom Saunders
Ceiling rough. Shannon is the contact Phone #: ###-#### >> Inspection requested via web by Deb Ipsen Inspection cancelled from web by: Deb Ipsen
Electrical Rough-In7/16/20197/17/20197/17/2019ACANC
DetailsTom Saunders
Hard lid ceiling rough in inspection.
Brett Jenkins is the contact Phone #: ###-#### Inspection requested via web by Deb Ipsen...ok to cover...3 bathrooms
Electrical Rough-In7/1/20197/3/20197/3/2019APASS
DetailsEric Story
rough in walls. Shannon or Brett will be onsite Phone #: ###-#### Inspection requested via web by Deb Ipsen
Walls only ok to cover
Electrical Rough-In7/1/20197/2/20197/1/2019ACANC
DetailsTom Saunders
Rough in wall, Shannon or Brett will be on site Phone #: ###-#### >> Inspection requested via web by Deb Ipsen Inspection cancelled from web by: Deb Ipsen
Electrical Rough-In4/23/20194/24/20194/24/2019APASS
DetailsTom Saunders
underground/ under slab inspection
Brett is the contact ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates..
ok to cover
Permanent Service3/19/20193/20/20193/20/2019ACANC
DetailsTom Saunders
Permanent service inspection for module building. Phone #: ###-#### Inspection requested via web by Shawna Gates...
wrong permit used...need seperate permit for permanent service pulled for modular building
Electrical Rough-In3/18/20193/19/20193/19/2019APASS
DetailsEric Story
Under ground inspection
Contact person is Brett Jenkins Phone #: ###-#### Inspection requested via web by Shawna Gates
U/G to out building for main power ok to cover
Electrical Rough-In3/14/20193/15/20193/15/2019APASS
DetailsTom Saunders
UFER GROUND. TATE IS THE CONTACT: ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates...
ok to cover
Issue PAID IN FULL permit  3/14/2019 DONE
Payment received via Govolutions
Application received  3/14/2019 DONE
This permit was created on the web by Shawna Gates