Final | 3/28/2019 | 3/29/2019 | 3/29/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Shawna Gates... ok to final
|
Permanent Service | 3/21/2019 | 3/21/2019 | 3/21/2019 | P | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Shawna Gates...done AM already...changed final to perm service
|
Final | 3/20/2019 | 3/21/2019 | 3/21/2019 | A | CANC |
Tom Saunders
|
|
|
the underground feeder are provided and installed by Idaho power, please remove the feeder issue from our inspection. We have know idea what size they are installing Phone #: ###-#### Inspection requested via web by Shawna Gates... needed permanent service inspection please schedule final when power restored
|
Permanent Service | 3/21/2019 | 3/21/2019 | 3/21/2019 | A | PASS |
Tom Saunders
|
|
|
the underground feeder are provided and installed by Idaho power, please remove the feeder issue from our inspection. We have know idea what size they are installing Phone #: ###-#### Inspection requested via web by Shawna Gates.... p/s u/g new ok
|
Final | 3/20/2019 | 3/20/2019 | 3/20/2019 | P | FAIL |
Eric Story
|
|
|
Module building service Phone #: ###-#### Inspection requested via web by Shawna Gates *Need grounding electrode system installed *Feeders shall be installed as well to verify sizing *AFC calc needed(fuses are being used may require on final)
|
Electrical Rough-In | 3/20/2019 | 3/20/2019 | 3/20/2019 | P | PASS |
Eric Story
|
|
|
U/G inspection ok to cover, was noted under ELE19-00895 before new permit pulled for power to out building
|
Issue PAID IN FULL permit | | | 3/20/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/20/2019 | | DONE |
|
|
|
This permit was created on the web by Shawna Gates
|