Final | 11/4/2019 | 11/5/2019 | 11/5/2019 | A | PASS |
Eric Story
|
|
|
Final ok for addition
|
Final | 11/4/2019 | 11/4/2019 | 11/4/2019 | P | CANC |
Eric Story
|
|
|
Ben Phone #: ###-####
|
Final | 10/31/2019 | 11/1/2019 | 11/1/2019 | A | FAIL |
Eric Story
|
|
|
Ben Phone #: ###-#### 210.52 REceptacle required within 24" of a range in both directions 210.8 GFCI protection required for all bathroom receptacles(Master bath) 210.12 AFCI protection for bedrooms(excersize room has rods in closets) 110.25 Lockable means of Disc for all hard wired appliances(oven) open ground in back rooms Hall bath receptacle in-op next to GFCI BCO-no violation shall be retained Replace flex and receptacle in front of house
|
Electrical Rough-In | 5/24/2019 | 5/28/2019 | 5/28/2019 | A | PASS |
Eric Story
|
|
|
Please call prior to heading to property for inspection. Property is locked so I will need to open. Requesting Rough-in/Cover Phone #: ###-#### Inspection requested via web by Ben Garner Whole house re-wire ok to cover
|
Application received | | | 3/21/2019 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 3/21/2019 | | DONE |
|
|
|
|