Print Statement | | | 11/6/2019 | | DONE |
|
|
|
|
First Notice | 7/31/2019 | 7/31/2019 | 8/20/2019 | | DONE |
Eric Story
|
|
|
This permit finaled on the web by Lee VanSchoiack
|
Final | 7/30/2019 | 7/31/2019 | 7/31/2019 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Occ card signed Final ok
|
Permanent Service | 7/12/2019 | 7/12/2019 | 7/12/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack p/s u/g n ok
|
Electrical Rough-In | 6/10/2019 | 6/10/2019 | 6/10/2019 | P | PASS |
Eric Story
|
|
|
ufer repair Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Damaged Uffer fixed with irreversible crimp installed ok to cover
|
Electrical Rough-In | 6/6/2019 | 6/7/2019 | 6/7/2019 | A | PART |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack UFER damagered. Need to repair before covering Below meter location. Ok to cover all areas except below meter
|
Electrical Rough-In | 4/29/2019 | 4/30/2019 | 4/30/2019 | A | PASS |
Eric Story
|
|
|
Concrete floor Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Corrections fixed as noted Concrete floor boxes ad conduit ok to cover
|
Electrical Rough-In | 4/29/2019 | 4/29/2019 | 4/29/2019 | P | FAIL |
Rock A. Hudson
|
|
|
concrete floor Phone #: ###-#### Inspection requested via web by Lee VanSchoiack 352.30(A)(B)- PVC shall be secured with in 3' of a termination and at interval not to exceed 10'.
|
Electrical Rough-In | 4/3/2019 | 4/3/2019 | 4/3/2019 | P | PASS |
Eric Story
|
|
|
Concrete walls Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Conduits in concrete wall for power and panel ok to pour
|
Electrical Rough-In | 3/23/2019 | 3/25/2019 | 3/25/2019 | A | PASS |
Rock A. Hudson
|
|
|
ufer ; ug conduit Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Basement area unclassified due to ventalation noted on print E2 general note 3. Basement inslab and concrete encased electrode conduit rough in ok cover
|
Issue PAID IN FULL permit | | | 3/23/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/23/2019 | | DONE |
|
|
|
This permit was created on the web by Lee VanSchoiack
|