Final | 5/23/2019 | 5/23/2019 | 5/23/2019 | P | PASS |
Rock A. Hudson
|
|
|
Hot tub ready for re inspection. Jason is our contact ###-####, Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin Final ok
|
Final | 5/15/2019 | 5/15/2019 | 5/15/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Hot tub wiring ready for final. Please call Jason at ###-#### when you are on the way. Thank you Phone #: ###-#### Inspection requested via web by Kelly Felin 680.22(A)(1)- A receptacle outlet shall be located with in 20' of waters edge but no closer than 6' of the spa or hot tub. 680.42(B)(4)- For hot tubs with top rim less than 28" above perimeter surfaces an equipotential bonding of perimeter surfaces is required.
|
Electrical Rough-In | 3/27/2019 | 3/27/2019 | 3/27/2019 | P | PASS |
Rock A. Hudson
|
|
|
Jason Gaythwaite is our journeyman and contact. the inspection is for underground trenching in the back yard. Landscapers will also be present Phone #: ###-#### Inspection requested via web by Kelly Felin Decking being replace completely around pool as well. Underground for hot tub rough in ok cover
|
Issue PAID IN FULL permit | | | 3/27/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/27/2019 | | DONE |
|
|
|
This permit was created on the web by Kelly Felin
|