First Notice | 8/1/2019 | 8/1/2019 | 10/1/2019 | | DONE |
Rock A. Hudson
|
|
|
|
Print Statement | | | 10/1/2019 | | DONE |
|
|
|
|
Final | 7/31/2019 | 8/1/2019 | 8/1/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok
|
Final | 7/30/2019 | 7/31/2019 | 7/31/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Corrections not complete. 110.22(A)- AC disconnecting means shall be identified as to which AC unit is controlled by which disconnect. 408.4- Panel 2 circuit directory not complete.
|
Conference | 7/30/2019 | 7/30/2019 | 7/30/2019 | P | PASS |
Rock A. Hudson
|
|
|
Discussed complete scope of work for office areas. Westerm and most eastern areas have circuitry added for office work stations. As of 12pn 7/30/19 Jimmy with Mountain power has been repairing items listed.
|
Final | 7/24/2019 | 7/24/2019 | 7/24/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez 110.3- A double duplex located in conference room not working. 210.63- A service 120 volt 15 or 20 amp receptacle shall be located with in 25' of AC unit. 314.23- Boxes shall be securely mounted. MC and boxes sitting on top of file cabinets. 314.25- 3 open boxes found in eastern open area shall have covers. 408.4- Panel 2 circuit directory shall be complete. 440.11- A disconnecting means shall be provided for newer AC unit. *BCC 4-05-32- Code violations not to be retained. Checked all unoccupied areas.
|
Electrical Rough-In | 3/28/2019 | 3/29/2019 | 3/29/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Perimeter walls rough in ok cover
|
Issue PAID IN FULL permit | | | 3/28/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 3/28/2019 | | |
|
|
|
|
Application received | | | 3/28/2019 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|