Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-01194
StatusFinaled
Name GEN 3 ELECTRIC LLC
Site Address 3152 S FALLING BROOK LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Trim out of house.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/25/20194/26/20194/26/2019APASS
DetailsRock A. Hudson
Door lock box code: 5584 Phone #: ###-#### Inspection requested via web by Nick Avery Final ok
Final4/19/20194/22/20194/22/2019AFAIL
DetailsRock A. Hudson
Code for door lock box 5584. Phone #: ###-#### Inspection requested via web by Nick Avery 210.11- Bathroom receptacle outlets shall be fed by a dedicated 20 amp circuit as noted to previous contractor on 6-15-18.
210.52- A receptacle outlet shall be located with in 24" of left side of kitchen sink.
314.20- Where boxes are mounted in non combustible wall cover and are recessed more than 1/4" a spark ring shall be installed.
408.4- Circuit directory shall accurately describe circuitd function.
*Dining light hanging on wires, several lights not working.
Issue PAID IN FULL permit  4/4/2019 DONE
Payment received via Govolutions
Application received  4/4/2019 DONE
This permit was created on the web by Nick Avery