First Notice | 7/2/2019 | 7/2/2019 | 9/30/2019 | | DONE |
Eric Story
|
|
|
This permit finaled on the web by Tyler Bowen
|
Final | 7/1/2019 | 7/2/2019 | 7/2/2019 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen Items as noted corrected... Occ card signed
|
Final | 6/28/2019 | 7/1/2019 | 7/1/2019 | A | PART |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen 440.22C Max overcurrent shall not exceed manufacturer values.( 2 RTU's fused at 20A need 15A, Mini split fused at 30A needs 20A) Partial final only ok
|
Electrical Rough-In | 6/19/2019 | 6/20/2019 | 6/20/2019 | A | PASS |
James Ady
|
|
|
ceiling cover for remaining two high ceilings. Phone #: ###-#### Inspection requested via web by Tyler Bowen 14ft ceiling only ok to cover
|
Electrical Rough-In | 6/13/2019 | 6/14/2019 | 6/14/2019 | A | PASS |
James Ady
|
|
|
Ceiling Cover - Low Ceiling Phone #: ###-#### Inspection requested via web by Tyler Bowen Ceiling only Marked on lighting print. Side A or South sided
|
Permanent Service | 6/3/2019 | 6/4/2019 | 6/4/2019 | A | CANC |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen
|
Electrical Rough-In | 6/4/2019 | 6/4/2019 | 6/4/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen Checked Grounding/Bonding of tranfsormers. Ok to energize
|
Electrical Rough-In | 5/1/2019 | 5/3/2019 | 5/3/2019 | A | PASS |
James Ady
|
|
|
Wall Cover Phone #: ###-#### Inspection requested via web by Tyler Bowen Remaining interior office walls only ok to cover
|
Electrical Rough-In | 4/24/2019 | 4/26/2019 | 4/26/2019 | A | PASS |
Eric Story
|
|
|
Wall Cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy Exterior walls and conference room and extrerior offices minus interoir ok to cover
|
Electrical Rough-In | 4/8/2019 | 4/8/2019 | 4/8/2019 | P | PASS |
James Ady
|
|
|
underground floor box and east walls. Phone #: ###-#### Inspection requested via web by Tyler Bowen East wall and underground in conference rooms ok to cover
|
Issue PAID IN FULL permit | | | 4/8/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/8/2019 | | DONE |
|
|
|
This permit was created on the web by Tyler Bowen
|