First Notice | 7/12/2019 | 7/12/2019 | 5/15/2020 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Deb Gooden
|
Final | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | PASS |
Rock A. Hudson
|
|
|
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok
|
Final | 7/9/2019 | 7/10/2019 | 7/10/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden 210.12- All outlets located in bedrooms shall have AFCI protection. Smokes, switches and receptacles. 406.12- All 15 and 20 120 volt receptacle outlets installed in a dwelling unit shall be tamper resistant type. 422.30- All hardwired appliances shall have a disconnecting means. 110.25 lock outs acceptacle. Hood.
|
Issue PAID IN FULL permit | | | 4/12/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/12/2019 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|