Final | 4/18/2019 | 4/18/2019 | 4/18/2019 | P | PASS |
Tom Saunders
|
|
|
Corbin Metcalf ###-#### Gate on the right side Phone #: ###-#### Inspection requested via web by Samatha Solberg... corrections made...ok to final
|
Final | 4/17/2019 | 4/17/2019 | 4/17/2019 | P | FAIL |
Tom Saunders
|
|
|
Justin Metcalf ###-#### The AC unit is on the right side, go through the gate. Phone #: ###-#### Inspection requested via web by Samatha Solberg... 1) panel shall be labelled completely and legibilly 2) all openings in panel shall be closed...panel blank or spare breaker 3) a service outlet shall be within 25ft of A/C unit
|
Issue PAID IN FULL permit | | | 4/17/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/17/2019 | | DONE |
|
|
|
This permit was created on the web by Samatha Solberg
|