Electrical Rough-In | 5/14/2019 | 5/14/2019 | 5/14/2019 | P | PASS |
James Ady
|
|
|
Re-inspection of kitchen. Please call or text prior, thank you. Phone #: ###-#### Inspection requested via web by Troy Nichols Corrections made kitchen rough in ok
|
Electrical Rough-In | 5/9/2019 | 5/10/2019 | 5/10/2019 | P | PASS |
James Ady
|
|
|
Please text or call prior to arrival, thank you. Phone #: ###-#### Inspection requested via web by Troy Nichols Need to add circuit for range hood, Add 2nd small appl. circuit and seperate counter top rreceps, Need deeper boxes for cooktop and double oven, Remove disp. from small appl. circuit and feed from dish. circuit. Do Not Cover Kitchen. Dining, sun and living rooms ok to cover
|
Conference | 4/28/2019 | 4/29/2019 | 4/29/2019 | A | DONE |
Rock A. Hudson
|
|
|
Conference on fixtures and removal of old knob and tube wiring. Phone #: ###-#### Inspection requested via web by Troy Nichols Pamphlet given, discussed receptacle layout for habitable rooms and kitchen counter top areas. Removing all knob and tube and rewiring all level 1.
|
Permanent Service | 4/26/2019 | 4/26/2019 | 4/26/2019 | P | PASS |
Rock A. Hudson
|
|
|
Owner to replace grounding electrode to underground water pipe with #4 ground as per 250.66 and secure panel to wall better. p/s o/h rec ok
|
Permanent Service | 4/25/2019 | 4/26/2019 | 4/25/2019 | A | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by Troy Nichols Inspection cancelled from web by: Troy Nichols
|
Conference | 4/19/2019 | 4/22/2019 | 4/22/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Nichols talked about grounding, Feeder conductor size, Weather head, when to call for inspection. Also informed owner to call ID power to schedule disc. amd reconnect.
|
Issue PAID IN FULL permit | | | 4/19/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/19/2019 | | DONE |
|
|
|
This permit was created on the web by Troy Nichols
|