Permit Information
Permit NumberELE19-01482
StatusFinaled
Name PRIME ELECTRICAL LLC
Site Address 3711 S COUNCIL SPRING RD
Project Name 
Customer Number1663
ePlanReviewNo
Description
New: electrical work for new apartments
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/10/201912/11/201912/11/2019APASS
DetailsJames Ady
All previous findings have been addressed and fixed. We are needing a final electrical inspection for the apartment buildings (the parking lot will have its own permit, which is being pulled now inspections for that portion of the project (parking lot) will be requested at a later date. At this point in time we need a passed final electrical for the buildings. Code is 1415 if needed. Please call Jared ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Angela Stears Parking lot will be completed under ELE19-04746. Corrections have been made final ok
Final11/14/201911/15/201911/15/2019APART
DetailsJames Ady
Final electrical inspection needed for roof and exterior Please call Jared with any questions. Phone #: ###-#### Inspection requested via web by Angela Stears Partial only. Exterior light is up, Unit 104 Mini split has a 15A max ocpd. 20A installed. Partial final ok (Note: HVAC contractor had been trouble shooting problems in Mini spit rooftop units. Many cover for lowvolt connections were missing screws.)
Electrical Rough-In11/8/201911/12/201911/12/2019APASS
DetailsJames Ady
Front parking lot underground inspection please Phone #: ###-#### Inspection requested via web by Angela Stears Builder is bringing grade up and assures ther will be 24in above all conduits. Underground to car port ok to cover
Final11/1/201911/4/201911/4/2019APART
DetailsJames Ady
ALL units are ready for final electrical inspection as well as both stairwells and the 3 garages. The garage code is 1215. Call Jared with any questions ###-#### Phone #: ###-#### Inspection requested via web by Angela Stears Unit 304 Bath heater not installed properly, Patio W/P not working.Garage missing 1 exterior light on west wall. Need to check rooftop and parking lot lighting when complete. Partial final only
Final10/31/201911/1/201911/1/2019AFAIL
DetailsJames Ady
Right Stairwell Units ready for final inspection #103, #104, #203,#204, #303 and #304 thank you Phone #: ###-#### Inspection requested via web by Angela Stears 103. Burried washer recep, Dryer cord connector clamped on open conducters, Missing Dish stub, Dish/disp Lockout, Dining receps dead. Did not finish inspecting units. Too many missed items leading me to believe job had not been checked prior to inspection. Informed contractor that Dry cords, range cords and Dishwasher connections will be cheked in all units prior to final for abrasion protection and proper install of connectors.
Final10/29/201910/30/201910/30/2019AFAIL
DetailsRock A. Hudson
Electrical final inspection needed for "left stairwell units" #301, #302, #201,#202, #101 and #102 Thank you Phone #: ###-#### Inspection requested via web by Angela Stears
110.3- Panel cover door shall be complete as per listing. 101.
210.52(C)- Receptacle outlets installed to serve kitchen counter top space at end of peninsula shall not be locatedmre than 6" back under overhang. All units.
408.4- Circuit directory shall be complete. 101.
Rough-In Permanent Service5/15/20195/15/20195/15/2019PPASS
DetailsJames Ady
Underground inspection on the SW corner of the building from the service around the corner. Phone #: ###-#### Inspection requested via web by Angela Stears underground ok
Rough-In Permanent Service5/1/20195/2/20195/2/2019APASS
DetailsJames Ady
1st floor rough inspection. As well as service inspection for all floors. Phone #: ###-#### Inspection requested via web by Angela Stears 1st floor ok to cover. p/s u/g n ok 13 meters
Electrical Rough-In4/26/20194/29/20194/29/2019APASS
DetailsEric Story
Floor 2 rough in inspection please Phone #: ###-#### Inspection requested via web by Angela Stears
2nd floor units ok to cover
Electrical Rough-In4/23/20194/24/20194/24/2019APASS
DetailsJames Ady
3rd floor inspection requested Phone #: ###-#### Inspection requested via web by Angela Stears 3rd floor only Cables ran for mini split are listed "Mini splt" cable. 14-4 300volt rated. Outdoor rated. rough in ok
Issue PAID IN FULL permit  4/23/2019 DONE
Payment received via Govolutions
Application received  4/23/2019 DONE
This permit was created on the web by Angela Stears
First Notice12/11/201912/11/2019   
DetailsJames Ady