Final | 7/10/2019 | 7/11/2019 | 7/11/2019 | A | PASS |
Eric Story
|
|
|
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson Final ok
|
Final | 7/2/2019 | 7/3/2019 | 7/3/2019 | P | CANC |
Tom Saunders
|
|
|
access: 1027 Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Electrical Rough-In | 4/29/2019 | 4/30/2019 | 4/30/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson... corrections made...perm service inspection required to be scheduled along with rough-in has been added for this inspection but will not be in future..contractors responsibility rough ok to cover
|
Permanent Service | 4/30/2019 | 4/30/2019 | 4/30/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson... p/s u/g new ok
|
Electrical Rough-In | 4/25/2019 | 4/26/2019 | 4/26/2019 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson... 1) intersystem bond needs added at service 2) exterior can lights wiring need clearance from roof...1 1/4" 3) metal boxes shall be grounded 4) wire outside wall
|
Issue PAID IN FULL permit | | | 4/25/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/25/2019 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|