Print Statement | | | 11/14/2019 | | DONE |
|
|
|
|
First Notice | 6/7/2019 | 6/7/2019 | 10/1/2019 | | DONE |
Rock A. Hudson
|
|
|
|
Print Statement | | | 10/1/2019 | | DONE |
|
|
|
|
Final | 6/7/2019 | 6/7/2019 | 6/7/2019 | P | PASS |
Rock A. Hudson
|
|
|
Gfci recaps installed ready for re inspection Phone #: ###-#### Inspection requested via web by Kevin Oderkirk Final ok
|
Final | 6/6/2019 | 6/6/2019 | 6/6/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Ready for final Phone #: ###-#### Inspection requested via web by Kevin Oderkirk 210.8- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Break room 3 receptacles with in 6'.
|
Electrical Rough-In | 4/25/2019 | 4/26/2019 | 4/26/2019 | A | PASS |
Tom Saunders
|
|
|
Call ###-#### Ed can show you where the work was done Phone #: ###-#### Inspection requested via web by Kevin Oderkirk.. new breakroom walls upstairs back of building go in exterior door marked 11000 ok to cover
|
Issue PAID IN FULL permit | | | 4/25/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/25/2019 | | DONE |
|
|
|
This permit was created on the web by Kevin Oderkirk
|