Temporary Service | 5/3/2019 | 5/3/2019 | 5/3/2019 | P | PASS |
Rock A. Hudson
|
|
|
3rd time is a charm. Phone #: ###-#### Inspection requested via web by Shawna Gates t/s o/h n ok
|
Temporary Service | 5/2/2019 | 5/3/2019 | 5/3/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Shannon is the contact again Phone #: ###-#### Inspection requested via web by Shawna Gates Corrections not complete
|
Temporary Service | 5/1/2019 | 5/2/2019 | 5/2/2019 | A | FAIL |
Rock A. Hudson
|
|
|
temporary service for construction site. Shannon is the contact person. Phone #: ###-#### Inspection requested via web by Shawna Gates 210.21- Overcurrent protection shall not axceed rating of receptacle. 40 amp installed. 590.6- All receptacles other than 120 volt shall have GFCI protection. Standard 240 installed on 50 amp receptacle.
|
Issue PAID IN FULL permit | | | 4/30/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/30/2019 | | DONE |
|
|
|
This permit was created on the web by Shawna Gates
|
First Notice | 5/3/2019 | 5/3/2019 | | | |
Rock A. Hudson
|
|
|
|