Final | 2/6/2020 | 2/7/2020 | 2/7/2020 | A | PASS |
Tom Saunders
|
|
|
garage code is 9239 10-2 was the old well wire before moved to other side of wall Phone #: ###-#### Inspection requested via web by Kevin Heideman...ok to final
|
Final | 2/5/2020 | 2/6/2020 | 2/6/2020 | A | FAIL |
Rock A. Hudson
|
|
|
garage code is 9239 Phone #: ###-#### Inspection requested via web by Kevin Heideman 210.71- Each mandoor with grade level access shall have an exterior luminaire installed. Master bed mandoor open box at time of inspection. 300.15- All cables shall terminate in a box. 10-2 garage wall left of furnace just pushed back in wall.
|
Rough-In Permanent Service | 5/8/2019 | 5/8/2019 | 5/8/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Heideman corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 5/6/2019 | 5/7/2019 | 5/7/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Heideman 300.14- A minimum of 6" of free conductor length shall be provided from where conductor emerges from sheath for splicing. Several found, check all and provide. 314.25- Recessed can junction box covers shall be installed to totally enclose opening on junction box. 3 found, 1 in kitchen, 1 in master bathroom, 1 in west hall. 334.30- Nm cable shall be secured with in 12" of a box. West hall desk area.
|
Issue PAID IN FULL permit | | | 5/1/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/1/2019 | | DONE |
|
|
|
This permit was created on the web by Kevin Heideman
|