Final | 6/13/2019 | 6/13/2019 | 6/13/2019 | P | PASS |
Mark Moncarr
|
|
|
Pump panel Phone #: ###-#### Inspection requested via web by Kevin Heideman Ok final.
|
Permanent Service | 5/2/2019 | 5/3/2019 | 5/3/2019 | A | PASS |
Mark Moncarr
|
|
|
its located between ashgrove ln and the fence. there is a gate there, I will leave the gate open. if you have any questions please call thanks Phone #: ###-#### Inspection requested via web by Kevin Heideman p/s u/g n ok
|
Conference | 5/3/2019 | 5/3/2019 | 5/3/2019 | A | DONE |
Mark Moncarr
|
|
|
Talked to electrician about possibly needing an equipotential ring around service that will be feeding an irrigation pump. 682.33(A) explains that if a service feeds a pump in or on water, it needs to have a 6' diameter ring placed in ground between 4" and 6". #8 bare or insulated minimum.
|
Issue PAID IN FULL permit | | | 5/2/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/2/2019 | | DONE |
|
|
|
This permit was created on the web by Kevin Heideman
|