Final | 8/5/2019 | 8/6/2019 | 8/6/2019 | A | PASS |
James Ady
|
|
|
Please call Sylvia ###-#### with at least a 30 minute heads up to meet you there. If you have any questions please feel free to contact Sam ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Corrections made final ok
|
Final | 8/2/2019 | 8/5/2019 | 8/5/2019 | A | FAIL |
James Ady
|
|
|
Homeowner will be home. Call Sam with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan 210.53C3 Peninsular caountertop 24in or longer shall have recep.
|
Electrical Rough-In | 5/16/2019 | 5/17/2019 | 5/17/2019 | A | PASS |
James Ady
|
|
|
Please call Tim ###-#### on your way to make sure he is home. If you have any questions please feel free to contact Sam ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Grounding verified and corrections made Kitchen rough in ok to cover
|
Electrical Rough-In | 5/14/2019 | 5/15/2019 | 5/15/2019 | P | FAIL |
James Ady
|
|
|
Call Tim ###-#### on your way to make sure he is home. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 210.52C1. No more than 48in between receps.(Rt and Lt of cooktop in corners) No more than 24in from wall break to recep.(Rt of fridge). 250.32. Services shall have grounding electrode system. ( Ground was connected to copper water line. Replaced with pex. Need to install grounding electrode system)
|
Issue PAID IN FULL permit | | | 5/7/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/7/2019 | | DONE |
|
|
|
This permit was created on the web by Clayton Morgan
|