Final | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | PASS |
Mark Moncarr
|
|
|
Talked to Electrician, he did not move 100a brkr yet. Rescheduled from 9/30 ###-#### Ok final.
|
Final | 9/29/2019 | 9/30/2019 | 9/30/2019 | P | CANC |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Tim Dunlop Rescheduled for 10/1
|
Electrical Rough-In | 7/29/2019 | 7/29/2019 | 7/29/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tim Dunlop Permanent service completed in May. Sub feed to garage installed as well as 2nd ground rod installed at garage complete. Must relocate garage breaker at meter main on house, 100 amp breaker installed on breaker space with 50 amp max rating. Sub feed and grounding rough in ok cover.
|
Rough-In Permanent Service | 7/28/2019 | 7/29/2019 | 7/29/2019 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tim Dunlop Needed rough in inspection for subfeed to garage and grounding electrode completion.
|
Electrical Rough-In | 7/15/2019 | 7/16/2019 | 7/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
electrical rough in Phone #: ###-#### Inspection requested via web by Tim Dunlop 250.53- A single ground rod shall have a suppemental rod installed unless proven less that 25ohms to ground by final. #8 SER 40amp max installed for range circuit. Rough in ok cover
|
Electrical Rough-In | 6/19/2019 | 6/19/2019 | 6/19/2019 | P | PASS |
Mark Moncarr
|
|
|
underground inspection for trench Phone #: ###-#### Inspection requested via web by Tim Dunlop Ok cover trench.
|
Rough-In Permanent Service | 5/30/2019 | 5/30/2019 | 5/30/2019 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Tim Dunlop p/s o/h n ok
|
(F) Reprint permit | | | 5/21/2019 | | DONE |
|
|
|
|
Conference | 5/7/2019 | 5/9/2019 | 5/9/2019 | A | DONE |
Mark Moncarr
|
|
|
Milenko Phone #: ###-#### Discussed service location for ADU
|
Issue PAID IN FULL permit | | | 5/7/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/7/2019 | | DONE |
|
|
|
This permit was created on the web by Tim Dunlop
|