Final | 6/12/2020 | 6/15/2020 | 6/15/2020 | A | PASS |
Tom Saunders
|
|
|
screened // Malcolm Phone #: ###-####... corrections made..ok to final
|
Final | 6/11/2020 | 6/12/2020 | 6/12/2020 | A | FAIL |
Eric Story
|
|
|
Screened- Malcon Phone #: ###-#### 1)Max overcurrent on A/C states 25/30 installed 2)W/R resistent receptacles for outdoors 3) GFCI for recept on furnace and has reverse polarity
|
Electrical Rough-In | 5/22/2019 | 5/23/2019 | 5/23/2019 | A | PASS |
Rock A. Hudson
|
|
|
malcom Phone #: ###-#### House rough in ok cover
|
Electrical Rough-In | 5/21/2019 | 5/22/2019 | 5/22/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Malcolm Phone #: ###-#### 210.11- Garage receptacle circuit shall have no other outlets. Garage lighting on with receptacles and 14 ga. wire installed as jumpers between lights and travellers in garage.
|
Conference | 5/13/2019 | 5/13/2019 | 5/13/2019 | P | DONE |
Eric Story
|
|
|
Malcom Phone #: ###-#### Will need to verify branch circuit in which 12g ran to areas and have 14g jumpers in between is on 15amp max breaker, Isolate grounded and grounding in both panels, re-check stapling throughout house
|
Application received | | | 5/13/2019 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 5/13/2019 | | DONE |
|
|
|
|