Permanent Service | 5/29/2019 | 5/30/2019 | 5/30/2019 | A | PASS |
James Ady
|
|
|
Reinspection-power off for over one year. Call Ryan for lock box code if needed. ###-#### Phone #: ###-#### Inspection requested via web by Ryan Schaffer p/s u/g rec ok
|
Permanent Service | 5/21/2019 | 5/22/2019 | 5/22/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Power off for over one year. Need inspection to turn power on. Please call Ryan for lock box code ###-#### Phone #: ###-#### Inspection requested via web by Ryan Schaffer 110.26(A)- Minimum work space shall be provided for meter base and both service disconnecting means of 30" wide and 36" deep. Remove evergreens to minimum required. 250.20- Services operating at 50 to 1000 volts shall be grounded. Unable to verify grounding electrode system and grounding electrode conductor installation. Meter base sealed and they are not located in either disconnecting means.
|
Issue PAID IN FULL permit | | | 5/21/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/21/2019 | | DONE |
|
|
|
This permit was created on the web by Ryan Schaffer
|