Final | 6/5/2019 | 6/7/2019 | 6/7/2019 | A | PASS |
Rock A. Hudson
|
|
|
final on hot tub inspection that needed a new plastic fixture installed. fixture has been replaced and picture sent to Darrell Phone #: ###-#### Inspection requested via web by A.M.E. Office As per Daryl DeGrange he has notes of item in question. Final ok
|
Final | 5/30/2019 | 5/31/2019 | 5/31/2019 | P | FAIL |
Daryl DeGrange
|
|
|
Please contact the customer before going out so they can leave work and be there when you come. Or Jamie Winters at ###-####. Phone #: ###-#### Inspection requested via web by A.M.E. Office NEC 680.23 Luminaire less than 5ft. shall be on GFCI protected branch circuit & 680.26(7) Bond gutter down spout. NEC 680.34 Required receptacle shall not be located less than 6ft. from hot tub
|
Issue PAID IN FULL permit | | | 5/30/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/30/2019 | | DONE |
|
|
|
This permit was created on the web by A.M.E. Office
|