Permanent Service | 6/4/2019 | 6/5/2019 | 6/5/2019 | P | PASS |
Tom Saunders
|
|
|
Installed second ground rod, intersystem bonding bar, and bonded hot and cold on water heater. Door code is 2730 Phone #: ###-#### Inspection requested via web by Dylan Pierce... corrections made P/s reconnect ok
|
Permanent Service | 5/31/2019 | 6/3/2019 | 6/3/2019 | A | FAIL |
Tom Saunders
|
|
|
Door code is 2730. Power has been off for over one year. Customer wants to energize before starting on renovations. Phone #: ###-#### Inspection requested via web by Dylan Pierce... grounding shall be brought up to code...2nd ground rod added and hot/cold water pipes need bonding
|
Issue PAID IN FULL permit | | | 5/31/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/31/2019 | | DONE |
|
|
|
This permit was created on the web by Dylan Pierce
|