Final | 7/8/2019 | 7/10/2019 | 7/10/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Please call Troy before heading that way, he works from home. The tech for this job is Brodie, please call with any questions ###-####. Phone #: ###-#### Inspection requested via web by William Salts Owner Troy ###-####. Panel located in a room that has been turned into a closet with shelf below and above panel and clothes rod installed. 110.26- Minimum work space of 30" wid and 36" deep shall be provided for panel. 240.24- Over current devices shall not be installed near easily igniteable materials such as clothes closets. Called and informed owner BLD13-00796 for the living space in garage had expired and to contact Bob Archibald to have permit reopened and then schedule BLD final once passed for occupancy would be able to request final on new ELE for mini-split. No inspection allowed until BLD final complete. Closet will need to be gutted completely to pass ELE final.
|
Final | 6/25/2019 | 6/26/2019 | 6/26/2019 | A | FAIL |
James Ady
|
|
|
Please call our office before heading that way. Call Brodie with any questions, customer will be on site. Phone #: ###-#### Inspection requested via web by William Salts MC shall be connected with listed connector.(Connection to indoor wall unit made by others.) BCC Section 9-05-32. No violation shall be retained.
|
Issue PAID IN FULL permit | | | 6/25/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/25/2019 | | DONE |
|
|
|
This permit was created on the web by William Salts
|